← Back to the Intze tank designer
What each part of the tank does, the formula that sizes it, the code table it comes from, and the rule of thumb to start with. Written so that someone new to tank design can follow it; every formula is the one the calculator uses.
Want the derivation behind a formula? See the formula reference — the same page the Theory links in the designer open.
In plain words: the water pushes outward on every surface. Parts that are stretched need steel rings; parts that are squeezed need only minimum steel. The Intze shape is arranged so that the two sloping parts at the bottom push on the girder in opposite directions and nearly cancel.
The columns stand on a circle under the bottom of the cone, not under the tank wall. Everything above them — roof, wall, cone, bottom dome and all the water — is carried down to the circular girder B₃ on top of the columns. This is the RDSO standard arrangement (drawing B-1235).
| Part | Along the slope / height | Round the ring | Steel |
|---|---|---|---|
| Top dome | squeezed | squeezed | minimum |
| Ring beam B₁ | — | stretched | designed |
| Cylindrical wall | squeezed (light) | stretched by water | designed hoops |
| Ring beam B₂ | — | stretched (cone + water) | designed |
| Conical slab | squeezed | stretched by water | designed hoops |
| Bottom dome (arches up) | squeezed | squeezed | minimum |
| Girder B₃ | bends and twists between columns | small hoop force left over | designed |
In plain words: decide how much water to store, then leave an empty gap at the top so an earthquake wave cannot hit the roof.
| Supply standard (CPHEEO Manual) | Litres / person / day |
|---|---|
| Towns with piped sewerage | 135 |
| Towns without sewerage | 70 |
| Rural piped supply (Jal Jeevan Mission) | 55 |
Freeboard must be at least the sloshing wave height from IS 1893 (Part 2):2014, dmax = (Ah)c × R × D/2 (see section 14). 0.3–0.6 m is typical; the calculator checks it.
In plain words: pick the ratios below, and the tank size follows from the capacity. These are starting values, not rules.
| Ratio | Classic textbook | RDSO type design (B-1235) | Calculator default |
|---|---|---|---|
| Cylinder height H₁ / D | about 0.4–0.6 | 0.32 | 0.32 |
| Bottom ring r / R | 5/8 = 0.625 | 0.66 | 0.66 |
| Cone slope from horizontal | 45° | 45° | 45° |
| Top dome rise / D | 1/8 = 0.125 | 0.165 | 0.165 |
| Bottom dome rise / r | 0.30–0.45 | 0.245 | 0.25 — then use the balancing value the design reports |
With the ratios fixed, V depends only on R, so R is found by trial (the calculator uses bisection).
| Load | Value used | Source |
|---|---|---|
| Reinforced concrete | 25 kN/m³ | IS 875 (Part 1) |
| Water | 9.81 kN/m³ | — |
| Roof live load | 1.5 kN/m² with access, 0.75 without | IS 875 (Part 2) |
| Finishes and fittings | 5–10% of the shell weight (8% default) | practice |
| Wind | see section 13 | IS 875 (Part 3):2015 |
| Earthquake | see section 14 | IS 1893 (Part 2):2014 |
Weight of a shell = surface area × thickness × 25. Surface areas: spherical dome 2πRdh, cylinder 2πRH₁, cone π(R + r) × slant length.
In plain words: parts that hold water are designed so the concrete does not crack and the steel is kept at a low stress. That is why the stresses below are much lower than in ordinary buildings.
| Grade | σcbc | σcc | direct tension σct | bending tension | m |
|---|---|---|---|---|---|
| M25 | 8.5 | 6.0 | 1.3 | 1.8 | 10.98 |
| M30 | 10.0 | 8.0 | 1.5 | 2.0 | 9.33 |
| M35 | 11.5 | 9.0 | 1.6 | 2.2 | 8.12 |
| M40 | 13.0 | 10.0 | 1.7 | 2.4 | 7.18 |
Compression: IS 456:2000 Table 21. Tension (resistance to cracking): IS 3370 (Part 2):2009 Table 1. m = 280 / (3σcbc).
| Bar | IS 3370 (Part 2):2009 | IS 3370:1965 (older) |
|---|---|---|
| Deformed (HYSD) | 130 | 150 |
| Plain mild steel | 115 | 115 |
IS 3370 (Part 2):2009 Cl. 4.4.3.1.
| Tank | Bar | L ≤ 14 m | Long members |
|---|---|---|---|
| Elevated | Fe 415 / 500 | 0.28% | 0.42% (L ≥ 28 m) |
| Elevated | Fe 250 | 0.44% | 0.66% (L ≥ 28 m) |
| On the ground | HYSD | 0.24% | 0.36% (L ≥ 22 m) |
Interpolate between the limits. L is the horizontal length of the continuous member between movement joints, along the main steel. An Intze tank has no joints, so L is the circumference of each member (2πR or 2πr) — for most tanks over 100 kL that means 0.42%. An Intze tank is elevated, so the ground-tank values do not apply.
The percentage is of each surface zone, in each direction. Surface zone = half the thickness, but not more than 250 mm. Walls under 160 mm and slabs under 180 mm may have all the steel in one face (Cl 8.1.2). Why the minimum depends on length ›
| M20 | M25 | M30 | M35 | M40+ |
|---|---|---|---|---|
| 2.8 | 3.1 | 3.5 | 3.7 | 4.0 |
In plain words: the roof is a shallow bowl upside down. Its weight squeezes it both ways, so the concrete takes the load and the steel is only the minimum.
Start with: rise D/8 to D/6, thickness 100–125 mm, minimum steel both ways.
In plain words: the dome pushes outward all round, like a barrel pushing on its hoop. Cut the ring in half: the outward push over the half is H × D, and the two cut ends share it.
Start with: 250–350 × 200–300 mm. If the check fails, widen the beam.
In plain words: water pressure grows with depth, so the wall is stretched most at the bottom. Horizontal bars take the stretch; the thickness is chosen so the concrete does not crack.
Note: this assumes the wall base is free to move outward. Where the wall is cast with the ring beam, the restraint causes vertical bending near the base; IS 3370 (Part 4) gives coefficients for it. Provide extra vertical steel on the water face at the bottom.
Start with: 150–300 mm. Hoop steel can be reduced in steps higher up.
In plain words: the cone below is squeezed, so at its top edge it pushes this ring outward. The water pushes the same way. Both add, which is why B₂ is usually the most heavily stretched ring.
Start with: 500–800 × 350–600 mm. The ring also restrains the bottom of the wall; generous size and a haunch at the junction are normal practice.
In plain words: the cone carries the wall and the water standing on it down to the girder, so along its slope it is squeezed. Round its circumference the water stretches it — and that stretch decides its thickness.
Start with: 45° slope, 200–400 mm.
In plain words: this dome arches up into the water from the girder, like a stone arch. The water on top squeezes it, and at its edge it kicks the girder outward — exactly opposite to the cone.
Rise: 0.22r–0.30r. The rise that exactly balances the cone is hb = r tan(φ₀/2), with tanφ₀ = W / (2πr × cone’s inward push). The calculator prints this value in section 8 of the results.
In plain words: when the cone’s inward push and the dome’s outward push nearly cancel, the girder has almost no ring force. It then works like a curved beam on columns: it sags between columns, hogs over them, and twists because it is curved.
| Columns | C₁ support | C₂ span | C₃ torsion | max torsion at |
|---|---|---|---|---|
| 6 | 0.01482 | 0.00751 | 0.001507 | 12.73° |
| 8 | 0.00827 | 0.00417 | 0.000628 | 9.53° |
| 10 | 0.00527 | 0.00265 | 0.000320 | 7.62° |
| 12 | 0.00365 | 0.00183 | 0.000184 | 6.35° |
Continuous circular beam, uniform load, equally spaced supports; angle measured from a support.
Start with: width ≥ column width; depth ≈ column spacing / 6 to / 8.
In plain words: take the wind speed for your district, adjust it for height, ground roughness, slope and cyclone risk, turn it into a pressure, and multiply by the area the wind sees.
| Height (m) | Cat. 1 | Cat. 2 | Cat. 3 | Cat. 4 |
|---|---|---|---|---|
| 10 | 1.05 | 1.00 | 0.91 | 0.80 |
| 15 | 1.09 | 1.05 | 0.97 | 0.80 |
| 20 | 1.12 | 1.07 | 1.01 | 0.80 |
| 30 | 1.15 | 1.12 | 1.06 | 0.97 |
| 50 | 1.20 | 1.17 | 1.12 | 1.10 |
IS 875 (Part 3):2015 Table 2 (interpolate between rows).
| Factor | Usual value |
|---|---|
| k₁ risk | 1.00 (50-year life); 1.07 important, 100-year |
| k₃ topography | 1.00 on flat ground; up to 1.36 on a hill crest |
| k₄ cyclone | 1.00 inland; 1.15 industrial / 1.30 post-cyclone importance in cyclonic coastal belts |
| Kd direction | 1.0 for the circular container; 0.9 for the frame |
| Ka area | 1.0 up to 10 m², 0.9 at 25 m², 0.8 at 100 m²+ |
| Cf container | 0.7–0.8 for the usual height/diameter |
Basic speeds: Kolkata 50, Delhi 47, Mumbai 44, Chennai 50, Bengaluru 33 m/s. Check the map in the code for your district.
In plain words: the lower water moves with the tank (the impulsive mass) while the upper water sloshes slowly (the convective mass). Each is a weight on a spring; work each out and combine them.
| Zone | II | III | IV | V |
|---|---|---|---|---|
| Z | 0.10 | 0.16 | 0.24 | 0.36 |
IS 1893 (Part 1):2016 Table 3. Kolkata III, Delhi IV, Guwahati V, Bengaluru II.
| Soil | Description | Sa/g for T > plateau (5%) |
|---|---|---|
| I | rock / hard, N > 30 | 1.00/T (plateau to 0.40 s) |
| II | medium, N 10–30 | 1.36/T (plateau to 0.55 s) |
| III | soft, N < 10 | 1.67/T (plateau to 0.67 s) |
Plateau value 2.5; for T < 0.1 s, 1 + 15T; beyond 4 s constant. IS 1893 (Part 1):2016.
| Factor | Value |
|---|---|
| Importance I | 1.5 drinking water / fire fighting; 1.0 others |
| R, RC frame staging (IS 13920 detailing) | 2.5 |
| R, RC shaft staging | 1.8 |
| Convective damping multiplier | 1.75 |
IS 1893 (Part 2):2014. Confirm R for your staging type in the code table.
In plain words: the sideways force tries to tip the tank. Columns on the far side get extra load, those on the near side lose load. With the tank empty, a strong enough force can even lift a column.
| Service — for the foundation |
|---|
| DL + water |
| DL + water + wind |
| DL + water + earthquake |
| DL + earthquake, tank empty |
| DL + wind, tank empty |
| Factored — for the members |
|---|
| 1.5 (DL + water) |
| 1.2 (DL + water + EQ) |
| 1.5 (DL + water) + 1.5 EQ |
| 1.5 (DL + water) + 1.5 wind |
| 0.9 DL + 1.5 EQ, tank empty |
| 0.9 DL + 1.5 wind, tank empty |
In plain words: spread the load wide enough that the soil pressure stays under what the soil can safely carry, and does not drop below zero (which would mean the foundation lifts).
Start with: raft width each side ≈ 0.3 × column circle diameter; thickness ≈ one-third of that width.
| Soil (indicative only) | Safe bearing, kN/m² |
|---|---|
| Soft clay | 50–100 |
| Medium clay, loose sand | 100–150 |
| Stiff clay, dense sand | 150–250 |
| Gravel, soft rock | 250 + |
Never design from this table. Use the soil investigation report for the site (IS 1892, IS 6403).
This guide supports the Nirmaanpro Intze tank designer. It summarises the codes for learning and preliminary design; always refer to the current editions of IS 456, IS 3370, IS 875, IS 1893, IS 11682 and IS 13920 for construction work.