Nirmaanpro

← Back to the Intze tank designer

Intze water tank: a compact design guide

What each part of the tank does, the formula that sizes it, the code table it comes from, and the rule of thumb to start with. Written so that someone new to tank design can follow it; every formula is the one the calculator uses.

Want the derivation behind a formula? See the formula reference — the same page the Theory links in the designer open.

1. How the tank carries its load

In plain words: the water pushes outward on every surface. Parts that are stretched need steel rings; parts that are squeezed need only minimum steel. The Intze shape is arranged so that the two sloping parts at the bottom push on the girder in opposite directions and nearly cancel.

The columns stand on a circle under the bottom of the cone, not under the tank wall. Everything above them — roof, wall, cone, bottom dome and all the water — is carried down to the circular girder B₃ on top of the columns. This is the RDSO standard arrangement (drawing B-1235).

PartAlong the slope / heightRound the ringSteel
Top domesqueezedsqueezedminimum
Ring beam B₁—stretcheddesigned
Cylindrical wallsqueezed (light)stretched by waterdesigned hoops
Ring beam B₂—stretched (cone + water)designed
Conical slabsqueezedstretched by waterdesigned hoops
Bottom dome (arches up)squeezedsqueezedminimum
Girder B₃bends and twists between columnssmall hoop force left overdesigned
top dome B₁ water B₂ cone bottom dome dome: out cone: in bracings columns on a circle of diameter 2r
Girder B₃ (orange) sits on the columns at the bottom of the cone.

2. Capacity and freeboard

In plain words: decide how much water to store, then leave an empty gap at the top so an earthquake wave cannot hit the roof.

Daily demand = population × per-capita supply
Overhead storage ≈ ¼ to ⅓ of daily demand (exact value from pumping hours by the mass-curve method)
Supply standard (CPHEEO Manual)Litres / person / day
Towns with piped sewerage135
Towns without sewerage70
Rural piped supply (Jal Jeevan Mission)55

Freeboard must be at least the sloshing wave height from IS 1893 (Part 2):2014, dmax = (Ah)c × R × D/2 (see section 14). 0.3–0.6 m is typical; the calculator checks it.

3. Proportions

In plain words: pick the ratios below, and the tank size follows from the capacity. These are starting values, not rules.

RatioClassic textbookRDSO type design (B-1235)Calculator default
Cylinder height H₁ / Dabout 0.4–0.60.320.32
Bottom ring r / R5/8 = 0.6250.660.66
Cone slope from horizontal45°45°45°
Top dome rise / D1/8 = 0.1250.1650.165
Bottom dome rise / r0.30–0.450.2450.25 — then use the balancing value the design reports
Water volume V = πR²hw + (πh₂/3)(R² + Rr + r²) − (πhb/6)(3r² + hb²)
hw = H₁ − freeboard · h₂ = (R − r) tanθ · the last term is subtracted because the bottom dome bulges up into the water.

With the ratios fixed, V depends only on R, so R is found by trial (the calculator uses bisection).

4. Loads

LoadValue usedSource
Reinforced concrete25 kN/m³IS 875 (Part 1)
Water9.81 kN/m³—
Roof live load1.5 kN/m² with access, 0.75 withoutIS 875 (Part 2)
Finishes and fittings5–10% of the shell weight (8% default)practice
Windsee section 13IS 875 (Part 3):2015
Earthquakesee section 14IS 1893 (Part 2):2014

Weight of a shell = surface area × thickness × 25. Surface areas: spherical dome 2πRdh, cylinder 2πRH₁, cone π(R + r) × slant length.

5. Materials and code tables

In plain words: parts that hold water are designed so the concrete does not crack and the steel is kept at a low stress. That is why the stresses below are much lower than in ordinary buildings.

Permissible concrete stresses (N/mm²)

Gradeσcbcσccdirect tension σctbending tensionm
M258.56.01.31.810.98
M3010.08.01.52.09.33
M3511.59.01.62.28.12
M4013.010.01.72.47.18

Compression: IS 456:2000 Table 21. Tension (resistance to cracking): IS 3370 (Part 2):2009 Table 1. m = 280 / (3σcbc).

Permissible steel stress, water-retaining parts

BarIS 3370 (Part 2):2009IS 3370:1965 (older)
Deformed (HYSD)130150
Plain mild steel115115

IS 3370 (Part 2):2009 Cl. 4.4.3.1.

Minimum steel (IS 3370 Part 2:2021, Cl 8.1.1, Table 5)

TankBarL ≤ 14 mLong members
ElevatedFe 415 / 5000.28%0.42% (L ≥ 28 m)
ElevatedFe 2500.44%0.66% (L ≥ 28 m)
On the groundHYSD0.24%0.36% (L ≥ 22 m)

Interpolate between the limits. L is the horizontal length of the continuous member between movement joints, along the main steel. An Intze tank has no joints, so L is the circumference of each member (2πR or 2πr) — for most tanks over 100 kL that means 0.42%. An Intze tank is elevated, so the ground-tank values do not apply.

The percentage is of each surface zone, in each direction. Surface zone = half the thickness, but not more than 250 mm. Walls under 160 mm and slabs under 180 mm may have all the steel in one face (Cl 8.1.2). Why the minimum depends on length ›

surface zone 1 (water face) surface zone 2 each zone gets its own minimum steel

Other rules

  • Concrete: M30 minimum for water-retaining RCC (IS 3370 Part 1).
  • Cover: 45 mm on faces in contact with water.
  • Maximum bar spacing: 300 mm, and not more than about three times the thickness.
  • Limit-state parts (girder, columns, footings): IS 456:2000.

Maximum shear stress τc,max (IS 456 Table 20)

M20M25M30M35M40+
2.83.13.53.74.0

6. Top dome

In plain words: the roof is a shallow bowl upside down. Its weight squeezes it both ways, so the concrete takes the load and the steel is only the minimum.

Dome radius Rd = (R² + h²) / 2h · sinθ = R/Rd
Load w = thickness × 25 + live load (kN/m²)
Meridional thrust T = wRd / (1 + cosθ)   (compression)
Hoop force = wRd [cosθ − 1/(1 + cosθ)]   (compression near the springing when θ < 51.8°)
Stress = T / t ≤ σcc
Outward push on B₁: H = T cosθ

Start with: rise D/8 to D/6, thickness 100–125 mm, minimum steel both ways.

Rd θ T (thrust) rise h base radius R

7. Top ring beam B₁

In plain words: the dome pushes outward all round, like a barrel pushing on its hoop. Cut the ring in half: the outward push over the half is H × D, and the two cut ends share it.

Hoop tension P = H × D/2 = H × R
Steel Ast = P / σst
Uncracked check: P / [Ac + (m − 1)Ast] ≤ σct

Start with: 250–350 × 200–300 mm. If the check fails, widen the beam.

H per metre, outward PP 2P = H × D

8. Cylindrical wall

In plain words: water pressure grows with depth, so the wall is stretched most at the bottom. Horizontal bars take the stretch; the thickness is chosen so the concrete does not crack.

Pressure at depth h: p = 9.81h
Hoop tension per metre height: F = p × D/2 = 9.81 h R
Steel Ast = F / σst, half on each face
Thickness t ≥ F (1/σct − (m−1)/σst), not less than 150 mm
Vertical steel = minimum steel

Note: this assumes the wall base is free to move outward. Where the wall is cast with the ring beam, the restraint causes vertical bending near the base; IS 3370 (Part 4) gives coefficients for it. Provide extra vertical steel on the water face at the bottom.

Start with: 150–300 mm. Hoop steel can be reduced in steps higher up.

p = 9.81 h small hoop force largest hoop force at the base

9. Ring beam B₂ (where the wall meets the cone)

In plain words: the cone below is squeezed, so at its top edge it pushes this ring outward. The water pushes the same way. Both add, which is why B₂ is usually the most heavily stretched ring.

Outward push from the cone = Nφ,top × sinα   (α = cone angle from the vertical)
Water on the beam face = 9.81 hw × beam depth
Hoop tension P = (sum) × R → Ast = P/σst; uncracked check as for B₁

Start with: 500–800 × 350–600 mm. The ring also restrains the bottom of the wall; generous size and a haunch at the junction are normal practice.

10. Conical slab

In plain words: the cone carries the wall and the water standing on it down to the girder, so along its slope it is squeezed. Round its circumference the water stretches it — and that stretch decides its thickness.

Along the slope (compression): Nφ = W / (2πrx cosα), W = everything above that level
Round the ring (tension): Nθ = (p / cosα + q tanα) × Dx/2
p = water pressure at that level, q = self weight per m² of slab
Check at the top (Dx = D) and the bottom (Dx = 2r); design for the larger
Thickness from the same uncracked check as the wall, not less than 200 mm

Start with: 45° slope, 200–400 mm.

water presses on the slab Nφ squeezes it down the slope girder B₃ here

11. Bottom dome

In plain words: this dome arches up into the water from the girder, like a stone arch. The water on top squeezes it, and at its edge it kicks the girder outward — exactly opposite to the cone.

Rd = (r² + hb²)/2hb, sinφ = r/Rd
Load W = water above it (less the bulge it displaces) + self weight
Meridional thrust Nφ = W / (2πr sinφ)   (compression)
Outward push on the girder = Nφ cosφ
Stress ≤ σcc; minimum steel both ways, each face

Rise: 0.22r–0.30r. The rise that exactly balances the cone is hb = r tan(φ₀/2), with tanφ₀ = W / (2πr × cone’s inward push). The calculator prints this value in section 8 of the results.

12. Circular girder B₃ and the Intze balance

In plain words: when the cone’s inward push and the dome’s outward push nearly cancel, the girder has almost no ring force. It then works like a curved beam on columns: it sags between columns, hogs over them, and twists because it is curved.

Net ring push = dome out + water on face − cone in  →  hoop force = net × r
W = everything above the columns (container + water + roof live load)
Msupport = C₁ W Rc · Mspan = C₂ W Rc · Tmax = C₃ W Rc (× 1.5 for design)
Torsion: equivalent moment Mt = T(1 + D/b)/1.7 and shear Ve = V + 1.6T/b (IS 456 Cl. 41)
ColumnsC₁ supportC₂ spanC₃ torsionmax torsion at
60.014820.007510.00150712.73°
80.008270.004170.0006289.53°
100.005270.002650.0003207.62°
120.003650.001830.0001846.35°

Continuous circular beam, uniform load, equally spaced supports; angle measured from a support.

Start with: width ≥ column width; depth ≈ column spacing / 6 to / 8.

hogging over columns sagging between them twisting near each column

13. Wind — IS 875 (Part 3):2015

In plain words: take the wind speed for your district, adjust it for height, ground roughness, slope and cyclone risk, turn it into a pressure, and multiply by the area the wind sees.

Vz = Vb k₁ k₂ k₃ k₄  ·  pz = 0.6 Vz² (N/m²)
pd = Kd Ka Kc pz  ·  F = Cf A pd
Staging frame: F = Cf As pd (1 + η) for the front frame plus the shielded rear frame

k₂ — height and terrain

Height (m)Cat. 1Cat. 2Cat. 3Cat. 4
101.051.000.910.80
151.091.050.970.80
201.121.071.010.80
301.151.121.060.97
501.201.171.121.10

IS 875 (Part 3):2015 Table 2 (interpolate between rows).

Other factors

FactorUsual value
k₁ risk1.00 (50-year life); 1.07 important, 100-year
k₃ topography1.00 on flat ground; up to 1.36 on a hill crest
k₄ cyclone1.00 inland; 1.15 industrial / 1.30 post-cyclone importance in cyclonic coastal belts
Kd direction1.0 for the circular container; 0.9 for the frame
Ka area1.0 up to 10 m², 0.9 at 25 m², 0.8 at 100 m²+
Cf container0.7–0.8 for the usual height/diameter

Basic speeds: Kolkata 50, Delhi 47, Mumbai 44, Chennai 50, Bengaluru 33 m/s. Check the map in the code for your district.

14. Earthquake — IS 1893 (Part 2):2014

In plain words: the lower water moves with the tank (the impulsive mass) while the upper water sloshes slowly (the convective mass). Each is a weight on a spring; work each out and combine them.

Equivalent cylinder: same D, depth h = V / (πD²/4)
mi/m = tanh(0.866 D/h) / (0.866 D/h) · mc/m = 0.23 (D/h) tanh(3.68 h/D)
Ti = 2π√[(mi + ms)/Ks], ms = container + ⅓ staging
Tc = Cc√(D/g) = 2π√[D / (3.68 g tanh(3.68 h/D))]
Ah = (Z/2)(I/R)(Sa/g); convective Sa/g × 1.75 (0.5% damping)
V = √(Vi² + Vc²), M = √(Mi² + Mc²) using hi*, hc* for overturning
Sloshing height d = (Ah)c R D/2 ≤ freeboard
Check both tank full and tank empty
mc mi staging Kₛ convective (sloshing) + impulsive
ZoneIIIIIIVV
Z0.100.160.240.36

IS 1893 (Part 1):2016 Table 3. Kolkata III, Delhi IV, Guwahati V, Bengaluru II.

SoilDescriptionSa/g for T > plateau (5%)
Irock / hard, N > 301.00/T (plateau to 0.40 s)
IImedium, N 10–301.36/T (plateau to 0.55 s)
IIIsoft, N < 101.67/T (plateau to 0.67 s)

Plateau value 2.5; for T < 0.1 s, 1 + 15T; beyond 4 s constant. IS 1893 (Part 1):2016.

FactorValue
Importance I1.5 drinking water / fire fighting; 1.0 others
R, RC frame staging (IS 13920 detailing)2.5
R, RC shaft staging1.8
Convective damping multiplier1.75

IS 1893 (Part 2):2014. Confirm R for your staging type in the code table.

Staging stiffness (rigid braces): Ks ≈ β × 12 n Ec Icol Np² / hs³
n columns, Np panels, β ≈ 0.85 for brace flexibility

15. Load combinations and column forces

In plain words: the sideways force tries to tip the tank. Columns on the far side get extra load, those on the near side lose load. With the tank empty, a strong enough force can even lift a column.

Column load = P/n ± M y / Σy², Σy² = (n/2) Rc²
Column moment ≈ (V/n) × panel height / 2 (portal method)
Service — for the foundation
DL + water
DL + water + wind
DL + water + earthquake
DL + earthquake, tank empty
DL + wind, tank empty
Factored — for the members
1.5 (DL + water)
1.2 (DL + water + EQ)
1.5 (DL + water) + 1.5 EQ
1.5 (DL + water) + 1.5 wind
0.9 DL + 1.5 EQ, tank empty
0.9 DL + 1.5 wind, tank empty
lateral load heaviest lightest

16. Columns and bracings

  • Number of columns: 6 up to about 200 kL, 8 for 200–600 kL, 10–12 above; keep 3–5 m between columns.
  • Column size: about 27 mm per metre of staging height to start, minimum 450 mm. Aim for 0.8–2.5% steel; above 4% make it bigger.
  • Design: IS 456 limit state for axial load with bending (P–M interaction). Effective length about 1.2 × panel height; if le/D > 12, add the slenderness moment PuD(le/D)²/2000.
  • Bracings: a level every 3.5–4 m. Moment from the column shear shared at each joint; shear = 2M/L for a member bent in double curvature.
  • Detailing: IS 13920 ductile detailing — closely spaced ties at every joint — is what allows R = 2.5.

17. Foundation

In plain words: spread the load wide enough that the soil pressure stays under what the soil can safely carry, and does not drop below zero (which would mean the foundation lifts).

Ring raft: A = π(Ro² − Ri²), Z = π(Ro⁴ − Ri⁴)/(4Ro)
Net pressure p = P/A − γDf ± M/Z
pmax ≤ SBC (× 1.25 for wind or earthquake cases, if the soil allows) · pmin ≥ 0
Raft bending as a cantilever from the column line: Mu = 1.5 pmax L²/2

Start with: raft width each side ≈ 0.3 × column circle diameter; thickness ≈ one-third of that width.

Soil (indicative only)Safe bearing, kN/m²
Soft clay50–100
Medium clay, loose sand100–150
Stiff clay, dense sand150–250
Gravel, soft rock250 +

Never design from this table. Use the soil investigation report for the site (IS 1892, IS 6403).

18. Final checklist

  1. Water volume matches the required capacity.
  2. Freeboard is more than the sloshing wave height.
  3. Wall and cone are thick enough for the uncracked check.
  4. Ring beams B₁ and B₂ pass the tension check.
  5. Dome stresses are below σcc.
  6. Girder: balance within about 35%, bending under Mlim, shear + torsion under τc,max.
  7. Columns: steel 0.8–4%, slenderness considered.
  8. No column in net tension, or the foundation is designed for uplift.
  9. Soil pressure under the allowed value in every case, and not negative.
  10. Earthquake and wind both carried through; tank empty checked.
  11. Minimum steel on every face; cover 45 mm on water faces.
  12. A licensed structural engineer has checked and signed the design.

This guide supports the Nirmaanpro Intze tank designer. It summarises the codes for learning and preliminary design; always refer to the current editions of IS 456, IS 3370, IS 875, IS 1893, IS 11682 and IS 13920 for construction work.

Open the Intze tank designer